EVDPlus is a controller featured two drivers for double pole stepper motor which manages two electronic expansion valves. EVDPlus controls refrigerant superheat and optimizes the efficiency of the refrigerant circuit, guaranteeing maximum flexibility, being compatible with various types of refrigerants and valves. It features low superheat (LowSH), high evaporation pressure (MOP), and low evaporation pressure (LOP) protection, and can manage, as an alternative to superheat control, special functions such as the hot gas bypass, evaporator pressure regulation (EPR) and control of the valve downstream of the gas cooler in transcritical CO2 circuits.
Universal EEV controller for two bi-polar valves
Two valves can be regulated independently
Supports 43+ refrigerants
Supports 0.5V~4.5V/4~20 mA type pressure sensor
Share With:
Description
Features
Documents
applications
Related
inquiry

Dual Bi-polar EEV universal controller

EVDPlus controller can be connected to either of the following:
• a UX* controller via RS485/Modbus;
• a supervisor or IoT platform via RS485/Modbus.
In this case, On/Off control is performed via digital input 1 for EEVA and digital 2 for EEVB, if suitably configured. As well as regulation start/stop, digital inputs 1 and 2 can be configured for the following:
– valve regulation optimization after defrosts;
– valve forced open (at 100%);
– regulation backup;
– regulation security.
Another possibility involves operation as a simple positioner with 4 to 20 mA or 0 to 10 Vdc analogue input signal.

EVDPlus has two build-in LED displays and one keypad with four keys, so that the user can change/configure

parameters easily. normally, the user just needs 4 parameters to start basic regulation:
• refrigerant
• Valve
• Pressure sensor
• main regulation

EVDPlus
EVDPlus

Features and benefits

One controller can manage 2 valves independently;
RS485 bus with standard Modbus RTU;
Compatibility with various types of valves;
Superheat control with protection functions for low superheat LowSH,MOP, LOP;
Build-in LED display and keypad, easy to check/change/config parameters;
Parameters protected with password;
Supports both 0.5V~4.5V and 4~20 mA pressure transducer;
Supports both NTC and PT1000 temperature probes;
4~20 mA or 0~10 Vdc input to use the controller as a positioner controlled by an external signal;
Management of power failures with valve closing (both 24Vac and 24Vdc);
Pre-position time settable by parameter;
4 to 20 mA pressure transducer can be shared between up to 5 drivers;